Hydrant and sprinkler systems
Differences, advantages and when they are mandatory
A complete guide for designers, investors and building managers
What is each system and how does it work?
🚒 Indoor Hydrant System
Indoor hydrants are fixed water supply points, installed in special cabinets on walls and connected to a pressurised pipe network. They are used manually by trained building staff or by firefighters to fight fires that have already started.
- Manual operation — requires a trained person to run out the hose and open the valve
- High water flow concentrated on one point — effective for active, developed fires
- Made up of: fire valve, semi-rigid or lay-flat hose, nozzle and protective cabinet
- Standard couplings for connecting fire engines (outdoor hydrants)
- Minimum pressure of 2.5 bar at the least favourable hydrant (per SR EN 671)
- Annual inspection and testing of the system is mandatory
💧 Sprinkler System
Sprinklers are automatic suppression heads installed in the ceiling, connected to a network of pipes filled with water (or air, in special versions). They activate individually and automatically when high temperature is detected — with no external signal and no human intervention.
- Fully autonomous operation — activates when the local temperature exceeds the set threshold (68°C, 79°C, 93°C, etc.)
- Each head activates independently — only the affected area receives water, not the whole building
- Fast response: the first heads activate within 1–4 minutes of the fire starting
- Types: wet systems (water permanently in the pipes), dry systems (compressed air), pre-action systems
- Designed to EN 12845 (European standard) or NFPA 13 (US standard)
- Require a dedicated water supply and a certified fire pump
Direct Comparison
- Manual operation by trained staff
- High flow: 2.1 – 6 l/s per hydrant
- Effective once the fire has spread
- Range: max. 30 m (hose + jet)
- Lower installation cost
- Maintenance: mandatory annual inspection
- Requires trained staff to operate
- Fully automatic operation, with no human intervention
- Moderate flow: 0.5 – 1.5 l/s per active head
- Effective in the early stage of a fire
- Even coverage of the entire protected area
- Higher installation cost
- Maintenance: six-monthly test + annual inspection
- Works 24/7, regardless of the human factor
The practical conclusion: hydrants are the firefighting tool, while sprinklers are the automatic prevention system. The best protection solutions combine both systems.
How does a sprinkler head work?
A common myth: “If one sprinkler goes off, the whole building gets flooded.” False. This is how it actually works:
Each sprinkler head contains a glass bulb filled with a heat-expanding liquid. When the rated temperature is reached (e.g. 68°C), the bulb breaks.
When the bulb breaks, it releases a deflector that spreads the water in a cone or parabola, covering an area of 9–12 m².
Only the heads directly exposed to the heat of the fire activate. The neighbouring heads stay closed — there is no “global command”.
Water flowing through the pipes triggers the fire alarm and sends a signal to the monitoring centre or the fire brigade, if the system is connected.
Statistically, 94% of fires are controlled with 4 or fewer active heads. Water damage is incomparably smaller than the damage from an uncontrolled fire.
Advantages and Limitations
Indoor Hydrants — Advantages
- ✓ High water flow — effective for fires that have already spread
- ✓ Lower installation cost than sprinklers
- ✓ Also useful for firefighters during their response
- ✓ Can also be used for other emergencies (industrial dust, minor incidents)
- ✓ No risk of accidental activation
Indoor Hydrants — Limitations
- ✗ Require trained staff to be present and available when the fire breaks out
- ✗ Ineffective at night or in unattended spaces
- ✗ Late response — the fire can spread before anyone acts
- ✗ Do not work in high or hard-to-reach spaces without special equipment
Sprinklers — Advantages
- ✓ Automatic response within minutes, regardless of the time or whether staff are present
- ✓ Dramatically reduce loss of life and property
- ✓ Selective activation — minimises collateral water damage
- ✓ May allow other protection measures (compartmentation, separation distances) to be reduced where regulations permit
- ✓ Insurers often offer lower premiums for buildings with sprinklers
Sprinklers — Limitations
- ✗ Significantly higher initial cost (design, equipment, installation)
- ✗ Require a dedicated water supply and a fire pump
- ✗ Risk of damage in case of accidental activation (faulty bulb, work in the area)
- ✗ Ineffective for gas or flammable liquid fires without special adaptation
- ✗ Mandatory, costly periodic maintenance
When are they mandatory? — Under Regulation P 118
The fire safety regulation P 118/2-2013 (fire suppression installations) and P 118/1-2018 clearly set out when each system becomes mandatory:
| Building type / Criterion | Indoor hydrants | Sprinklers |
|---|---|---|
| Civil buildings > 2,000 m² per floor or > 6 floors | Mandatory | Recommended / Mandatory* |
| High-rise and very high-rise buildings (>28 m) | Mandatory | Mandatory |
| Shopping centres >3,600 m² (gross floor area) | Mandatory | Mandatory |
| High fire risk warehouses >1,000 m² | Mandatory | Mandatory |
| High-risk industrial halls >2,500 m² | Mandatory | Mandatory |
| Hotels >4 floors or >100 beds | Mandatory | Mandatory |
| Hospitals, clinics, care homes | Mandatory | Mandatory |
| Underground car parks >3,000 m² | Mandatory | Mandatory |
| Small residential buildings (<G+2, <600 m²) | Not mandatory | Not mandatory |
* The exact requirement depends on the gross floor area, fire hazard category and height of the building. Consult an authorised designer for your specific situation.
📋 Reference regulations
- P 118/1-2018 — Fire safety regulation for buildings, Part I — Buildings
- P 118/2-2013 — Fire safety regulation for buildings, Part II — Fire suppression installations
- SR EN 12845:2015 — Fixed firefighting systems. Automatic sprinkler systems
- SR EN 671-1/2/3 — Fixed firefighting systems. Hose systems
- NP 086-05 — Regulation for the design, installation and operation of fire suppression installations
⚠️ Common mistakes in the design and operation of these systems
- Insufficient pressure at the hydrant — an undersized installation or a faulty pump makes the hydrant useless exactly when it is needed
- Blocked access to the hydrant cabinet — goods stored in front of the cabinet or the door painted over, situations often found in industrial halls
- Sprinklers installed below the minimum clearance above stored goods — in warehouses, the clear space below sprinklers (min. 0.45 m) is often ignored
- Painting sprinkler heads — a common practice during refurbishment that completely compromises their operation
- Lack of periodic maintenance — systems left unchecked for years can fail at the critical moment due to corrosion or damaged seals
- Using hydrants for other purposes (cleaning, watering plants) — lowers the network pressure and can compromise the integrity of the system
Conclusion: complementary, not alternatives
Indoor hydrants and sprinklers do not exclude each other — on the contrary, the most effective fire protection systems include both, each covering the gaps of the other:
- Sprinklers act immediately and automatically, limiting the fire in its early stage before firefighters arrive
- Hydrants allow a directed response by firefighters and trained staff to active or residual fires
- Together, they significantly reduce the likelihood of loss of life and minimise material damage
- Many regulations and insurers recognise this complementarity and reward it with reduced requirements or lower premiums
Correct design of both systems requires an authorised specialist to calculate flow rates, pressures and spray densities and to integrate everything with the building’s fire detection and alarm system.