A fire-rated wall can withstand fire for 60, 90 or 120 minutes — but if a pipe or a bundle of cables passes through it without proper sealing, that wall becomes useless within minutes. Untreated service openings are among the most common causes of rapid fire spread in otherwise well-designed buildings. Fire stopping of penetrations is not a finishing detail — it is a structural part of compartmentation.
80%
of fire deaths are caused by smoke and toxic gases, not by the flames themselves
EI 120
fire resistance required for compartment walls in high-rise buildings
0 mm
untreated gap allowed between a pipe/cable and the wall — every gap counts

Why is sealing penetrations critical?

Every modern building has dozens or hundreds of penetrations through walls and floors: water, gas and ventilation pipes, power cables, data cables, sprinkler systems. Each of them creates a gap in the fire compartmentation.

Without sealing, these gaps act as channels through which fire, smoke and hot gases spread much faster than through the wall itself — often within minutes of the fire starting.

What spreads through untreated gaps?

  • Smoke and toxic gases — the fastest and most dangerous factor; 80% of fire deaths are caused by smoke inhalation, not by flames
  • Heat — high temperatures can ignite combustible materials in the neighbouring compartment before the flames physically reach it
  • The flames themselves — slower, but inevitable if the gap is large enough or the surrounding materials are combustible
  • Metal pipes — steel or copper pipes conduct heat and can ignite materials in adjacent compartments even if the gap is small

⚠️ Warning: plastic pipes are a special risk

PVC, PP or PE pipes melt and burn when exposed to fire, widening the gap in the wall instead of blocking it. Without a seal using intumescent collars or special mortar, a 110 mm plastic pipe can create a fully open gap within 10–15 minutes, through which smoke and flames pass freely.

Solutions for plastic pipes are necessarily different from those for metal pipes or cables.

Fire stopping products — complete guide

There is no universal solution. The choice of product depends on the type of penetration, the pipe material, the size of the gap and the required fire resistance class. These are the main categories:

🔴
Intumescent Sleeves

Rings of intumescent material installed around the pipe, within the wall thickness. When heated, the material expands 8–10 times, compressing and sealing the gap left by the melting pipe.

Ideal use Plastic pipes (PVC, PP, PE) Ø 32–160 mm. Concrete, masonry and plasterboard walls and floors.
🟠
Fire Stopping Mortar

Cement- or gypsum-based mortar with fire-retardant additives, applied in large openings or in penetrations with several pipes/cables at once. Easy to apply, with no mechanical fixings needed.

Ideal use Large openings, multiple penetrations, combined cables and pipes. Repairs and refurbishment.
🟡
Intumescent Mastic / Sealant

Elastic material applied with a gun around pipes or cables and in joints between elements. It stays flexible after curing — ideal where there is vibration or thermal movement.

Ideal use Electrical cable penetrations, expansion joints, small and irregular gaps. Finishing and additional sealing.
🔵
Intumescent Pillows

Blocks/pillows of intumescent material installed in openings without being permanently fixed. Major advantage: they can be removed and reinstalled for later work on the installations.

Ideal use Cable penetrations that change frequently, technical areas with periodic access, large openings with variable density.
⚪
Mineral Wool + Mortar

Combined system: mineral wool (basalt or glass wool, melting point >1000°C) fills the gap and is then covered with fire stopping mortar. A robust solution for irregular openings.

Ideal use Metal pipe penetrations (hot water, steam, gas), large openings in concrete or masonry, thick walls.
🟢
Intumescent Collars

Similar to sleeves, but fitted on the outside face of the wall instead of inside it. They can be installed after the pipe is already in place, without breaking out the area around it.

Ideal use Refurbishment of existing buildings, where an internal sleeve can no longer be installed. Plastic pipes Ø 25–315 mm.

Which solution for which type of penetration?

Penetration type Material Recommended solution
Waste and drainage pipes PVC, PP (plastic) Intumescent sleeve / collar
Hot water / heating pipes Copper, steel, stainless steel Mineral wool + mortar
Natural gas pipes Steel Certified special mortar + mastic
Power cables (JY, NYY) PVC / XLPE insulation Mortar + intumescent mastic
Data / fibre optic cables PVC / LSZH sheath Intumescent pillows + mastic
Ventilation ducts Galvanised sheet steel Fire dampers + perimeter mortar
Sprinkler pipes Galvanised steel Metal sleeve + EI mortar
Combined penetrations (cables + pipes) Mixed Mortar + pillows + mastic (system)

How to install fire stopping correctly — step by step

The product matters, but the way it is installed is just as important. A certified product installed incorrectly does not provide the promised protection and can compromise the entire compartmentation system.

1
Identify and record all openings

Before any work starts, all service openings in compartment walls and floors must be identified and documented: dimensions, type of penetration, material and the fire resistance class required for the building element.

2
Clean and prepare the surface

The area around the opening must be cleaned of dust, grease and loose material. The surface must be dry and sound — fire stopping products do not bond properly to contaminated or damp surfaces.

3
Choose a certified product

The product must be certified to EN 1366-3 (service penetrations) or EN 1366-4 (fire dampers) and have a valid Declaration of Performance (DoP). The declared resistance class must equal or exceed the class of the wall/floor.

4
Install according to the technical data sheet

Each product comes with a specific technical data sheet stating the exact application depth, distance from the pipe, number of layers and tools required. Departing from the data sheet voids the certification.

5
Document the work

Every sealed penetration must be photographed and recorded in a works log. The documentation is needed for the fire safety (ISU) inspection and for later maintenance.

6
Visual marking

Good practice requires every seal to be clearly marked (label or pictogram) to make periodic inspections easier and prevent accidental damage during later works.

What does the fire authority (ISU) check at handover and inspections?

ISU inspectors check fire stopping both at the final handover of the building and during periodic inspections. This is what they look for specifically:

  • ✓ Seals are in place — every opening in compartment walls must be treated, without exception
  • ✓ Product certification — CE marking, Declaration of Performance, compliant fire resistance class
  • ✓ Installation according to the data sheet — depth, coverage, continuity
  • ✓ Installation records — photos, works log, declarations of conformity
  • ! Integrity at periodic inspections — damaged, cracked or partly removed seals are considered non-compliant
  • ! Openings created later — any work on installations that created new openings and was not followed by re-sealing is a serious non-compliance
  • ✗ Improvised solutions — ordinary polyurethane foam, non-approved glass wool, rags or other improvisations are not accepted and can lead to fines or suspension of activity

📋 Applicable regulations and standards

  • SR EN 1366-3 — Fire resistance tests for service installations. Penetration seals through walls and floors
  • SR EN 1366-4 — Fire dampers for ventilation systems
  • SR EN 13501-2 — Fire classification of construction products and building elements
  • P 118/1-2018 — Fire safety regulation (compartmentation requirements)
  • SR EN 15882-3 — Extended application of fire stopping test results for service penetrations
  • Regulation (EU) 305/2011 (CPR) — CE marking mandatory for all fire stopping products

⚠️ The most common mistakes we see on site

  • Polyurethane foam instead of certified fire stopping — standard PU foam burns and shrinks in heat, widening the gap. It is one of the most dangerous improvisations and, unfortunately, one of the most widespread
  • Intumescent sleeves installed too far from the wall — the maximum distance from the wall surface is usually 0 mm (flush). Any gap compromises performance
  • Openings created during refurbishment and left untreated — every time installations are modified (adding a cable, replacing a pipe), new openings are created and must be re-sealed immediately
  • Using a product for the wrong type of penetration — a sleeve certified for PVC is not valid for metal and vice versa. Certification is specific to each application
  • Mixing products from different manufacturers — fire stopping systems are tested and certified as complete systems. Replacing one component with another manufacturer’s product voids the certification
  • Missing installation records — without photos and a works log, proving compliance at ISU inspections becomes impossible

At what stage of construction is fire stopping carried out?

The ideal time to seal penetrations is immediately after the installations are fitted, before the finishes. Delaying creates practical problems and extra costs:

  • In new buildings — once pipes and cables are in their final position, before plastering or finishes. Access is easiest and costs are lowest
  • During refurbishment — whenever existing installations are modified. Any new opening must be sealed the same working day, not “at the end”
  • When the building’s use changes — compartmentation requirements may change; existing seals must be reassessed and, if necessary, replaced with higher-class solutions
  • At periodic inspections — seals should be visually checked at least once a year; damaged ones must be replaced immediately

Conclusion: fire stopping is the last link in compartmentation

A fire compartmentation system is only as strong as its weakest point. EI 90 or EI 120 certified walls and floors become useless if service openings are not treated correctly. Fire stopping is not an optional extra — it is a legal requirement and an essential safety element.

Choosing the right product for each type of penetration, installing it according to the data sheet and documenting the work properly are the three pillars of an effective fire stopping system that works when it really matters.

  • Use only certified products with CE marking and a valid DoP
  • Adapt the solution to the type of penetration — plastic, metal, cables and ventilation have different requirements
  • Document every seal — photos, works log, declarations of conformity
  • Don’t improvise with PU foam or other non-certified materials
  • Inspect regularly and re-seal any opening created by work on installations

Do you have untreated service openings in your building?